Outdoor Mounted Three - poles High Voltage Disconnect Switch With Steel Base Plate 126KV

Product Details

Place of Origin: Zhejiang,China(Mainland)

Brand Name: YONGDE

Certification: ISO9001, veiki

Model Number: JW-126

Payment & Shipping Terms

Minimum Order Quantity: 1pcs

Price: negotiation

Packaging Details: wooden case

Delivery Time: 21days per container

Payment Terms: T/T or western Union or L/C or PayPal, MoneyGram, D/P, D/A

Supply Ability: 1,000pcs per month

Get Best Price
High Light:

high voltage disconnectors

,

high voltage isolator switch

Type:
Earthing Switch
Max. Voltage:
126KV
Function:
Switching
Standard:
IEC 62271-102: 2005 IEEE Std C37.30-1997
Material:
Steel
Components:
Insulators
Type:
Earthing Switch
Max. Voltage:
126KV
Function:
Switching
Standard:
IEC 62271-102: 2005 IEEE Std C37.30-1997
Material:
Steel
Components:
Insulators
Outdoor Mounted Three - poles High Voltage Disconnect Switch With Steel Base Plate 126KV

Outdoor Mounted Three-poles Earthing Switches With Steel Base Plate 126KV

 

 

Why use YongDe earthing switches?

  • More than 24 years of experience
  • Durable and reliable design
  • High quality

 

Specifications:

 

Parameter Table
No Items Technical parameter
1 Rated Voltage kV   72.5 126 252
2 Nominal system voltage kV   66 110 220
3 Rated current A 630;1250;1600;2000;2500;3150;4000
4 Rated Short Time withstand current and Time kA/s 25~50/4
5 Rated Peak withstand current kA 63~125
6 1min power frequency withstand voltage (effective value) kV To earth 140 230 460
To phase 140 2300 460
Across Isolating DS 180 230+70 460+145
7 Lightning Impulse wishstand voltage(peak value) KV To earth 325 550 1050
To phase 325 500 1050
Across Isolating DS 385 550+100 1050+150
8 Rated mechanical terminal load N Level of lateral load 750 1500 2000
Level of vertical load 500 1000 1500
Vertical 750 1000 1250
9 The min distance of insulation against ground mm   600 1000 2000
10 Max Man Operative Moment N. m 200
11 Motor Drive operating mechanism control voltage V AC220,380; DC110,220
12 Motor Drive operating mechanism motor voltage V AC220,380; DC110,220

 

Testing:

 

The earthing switches are designed and tested in accordance with latest IEC specifications.