Product Details
Place of Origin: Zhejiang,China(Mainland)
Brand Name: YONGDE
Certification: ISO9001
Model Number: GW17-126
Payment & Shipping Terms
Minimum Order Quantity: 1pcs
Price: negotiation
Packaging Details: wooden case
Delivery Time: 21days per container
Payment Terms: T/T or western Union or L/C or PayPal, MoneyGram, D/P, D/A
Supply Ability: 1,000pcs per month
Product: |
Disconnector Switch |
Rated Voltage: |
126KV |
Function: |
Switching |
Standard: |
IEC 62271-102: 2005 IEEE Std C37.30-1997 |
Product: |
Disconnector Switch |
Rated Voltage: |
126KV |
Function: |
Switching |
Standard: |
IEC 62271-102: 2005 IEEE Std C37.30-1997 |
Horizontal Type Knee-type Disconnector Switch GW17-126
Description:
GW17-126 Type Disconnector Switch is good for reducing the distance and station arranging, especially for outdoor station.
Because of electric rod's self-rotation and switching structure and having self-locking function, it has strong property of motor performance resistance. Meanwhile, it can resist motor, wind pressure, earthquake and other outside power.
Specifications:
No | Item | Technical parameter | ||||||
1 | Rated Voltage kV | 72.5 | 123 | 145 | 245 | |||
2 | Rated Current A | 1250 1600 2000 2500 3150 4000 | ||||||
3 | Rated Short Time withstand current and Time kA/s | 25~50/4 | ||||||
4 | Rated Peak withstand current kA | 63~125 | ||||||
5 | 1min power frequency withstand voltage (effective value) kV | To earth | 140 | 230 | 275 | 460 | ||
To phase | 140 | 230 | 275 | 460 | ||||
Across Isolating DS | 180 | 300 | 315 | 605 | ||||
6 | Lightning Impulse wishstand voltage (peak value) kV |
To earth | 325 | 550 | 650 | 1050 | ||
To phase | 325 | 550 | 650 | 1050 | ||||
Across Isolating DS | 405 | 650 | 750 | 1200 | ||||
7 | Rated mechanical terminal load N | Level of lateral load | 750 | 1500 | 1500 | 2000 | ||
Level of vertical load | 500 | 1000 | 1000 | 1500 | ||||
Vertical | 750 | 1000 | 1000 | 1250 | ||||
8 | Capacity and Inductive Ability (open and close) | Capacity Current A | 1 | |||||
Inductive Current A | 0.5 | |||||||
9 | Max Man Operative Moment N. m | 200 | ||||||
10 | Motor Drive operating mechanism control voltage V | AC220; DC110, 220 | ||||||
11 | Motor Drive operating mechanism motor voltage V | AC220, 380; DC110, 220 |