Product Details
Place of Origin: Zhejiang,China(Mainland)
Brand Name: YONGDE
Certification: ISO9001/KEMA
Model Number: YH5W5-9
Payment & Shipping Terms
Minimum Order Quantity: 1pcs
Price: negotiation
Packaging Details: carton
Delivery Time: 21days per container
Payment Terms: T/T or western Union or L/C or PayPal
Supply Ability: 30,000pcs per month
Type: |
Metal Oxide Surge Arrester |
Material: |
Silicon Rubber |
Housing: |
Polymer |
Rated Voltage: |
9KV |
Accessory: |
Bracket,Insulating Cap,Cooper Lead,Insulator,Hoop |
Purpose: |
Over-Voltage Protection |
Structure: |
Self-Standing |
Color: |
Gray |
Type: |
Metal Oxide Surge Arrester |
Material: |
Silicon Rubber |
Housing: |
Polymer |
Rated Voltage: |
9KV |
Accessory: |
Bracket,Insulating Cap,Cooper Lead,Insulator,Hoop |
Purpose: |
Over-Voltage Protection |
Structure: |
Self-Standing |
Color: |
Gray |
9kV Polymeric Gapless Lightning Arrester with KEMA
Description:
YongDe Surge Arresters can be applied to a variety of systems including substation equipment, AC-DC converters, railway power system and power distribution units ranging from 0.25kV to 765kV systems. These surge arresters demonstrate excellent protection properties. YongDe surge arresters incorporate YNR elements (YongDe Non-linear Resistor ZnO Elements) with superior non-linear voltage-current characteristics, high quality and reliability. Metal oxide type surge arresters offer such special features inherent in the gap-less structure, such as a quick response to surge voltage, high energy dissipation capability, safe operation, compactness / lightweight and freedom from pollution.
Features:
1. Compact and Lightweight
2. Extremely Safe Pressure Relief Performance
3. Superior Performance against Environmental Contamination
4. Directly Molded Structure
5. Compliance with International Standards(IEC60099-4)
6. Simple Support Structure
7. Manufactured at Advanced ISO-9001 certified facilities
Applications:
1. Distribution networks
2. Transmission line
3. Substation
4. Railway power station
5. Alternator and electromotor
Specifications:
Type | YH5W5-9/24 |
Rated voltage---------kV | 9 |
MOCV ----------------kV | 7.65 |
Nominal Current-------kV | 5 |
Residual voltage of steep impulse----at 5kA(kV) | 26.5 |
8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) | 24 |
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV) | / |
1mA D.C reference voltage (kV) | 12.7 |
Line discharge level | 1 |
2mS long duration impulse current A | 250 |
4/10µS High current impulse kA | 65 |
Lightning impulse withstand kV | 75 |
Power frequency voltage withstand(dry/wet)kV | 28 |
0.1S TOV--------------kV | 10.8 |
1S TOV----------------kV | 10.35 |
10S TOV---------------kV | 9.9 |
1200S TOV-------------kV | 9 |
Creepage distance ----mm | 338 |
Material employed in series non-linear resistor | Zinc Oxide |
Working condition:
1) Environment temperature: -40--+40 degree
2) altitude: <1000m
3) 48HZ
4) Power frequency voltage should not be more than continuous running voltag
5) Max wind speed should be less than 35m/s
6) Earthquake intensity should be less than 7 degree
7) If used in contamination area, should be noted in advance.