Home ProductsMetal Oxide Surge Arrester

Hangzhou Yongde Electric Appliances Co.,Ltd

Good quality Lightning Surge Arrester for sales
Good quality Lightning Surge Arrester for sales

——

I'm Online Chat Now

18KV Silicon Rubber Metal Oxide Station Class Surge Lightning Arresters for Transformer Protection

China 18KV Silicon Rubber Metal Oxide Station Class Surge Lightning Arresters for Transformer Protection supplier

Large Image :  18KV Silicon Rubber Metal Oxide Station Class Surge Lightning Arresters for Transformer Protection

Product Details:

Place of Origin: Zhejiang,China(Mainland)
Brand Name: YONGDE
Certification: ISO9001/KEMA
Model Number: YH10W5-18/49.5

Payment & Shipping Terms:

Minimum Order Quantity: 1pcs
Price: negotiation
Packaging Details: carton
Delivery Time: 21days per container
Payment Terms: T/T or western Union or L/C or PayPal
Supply Ability: 30,000pcs per month
Contact Now
Detailed Product Description
Model: YH10W5-18/49.5 Material: Silicon Rubber
Housed: Polymer Rated Voltage: 33KV
Parts: Bracket,Insulating Cap,Cooper Lead,Insulator,Hoop Purpose: Over-Voltage Protection
Color: Customized Standard: IEC60099-4

18KV Silicon Rubber Metal Oxide Station Class Surge Lightning Arresters for Transformer Protection

 

Description:

 

Polymer surge arrester is a device to protect electrical equipment from over-voltage transients caused by external (lightning) or internal (switching) events. Also called a surge protection device (SPD) or transient voltage surge suppressor (TVSS), thisclass of device is used to protect equipment in power transmission and distribution systems. (For consumer equipment protection, different products called surge protectors are used.) The energy criterion for various insulation material can be compared by impulse ratio, the surge arrester should have a low impulse ratio, so that a surge incident on the surge arrester may be bypassed, to the ground instead of passing through the apparatus.

 

Technical Specifications:

 

Type YH10W5-18/49.5
Rated voltage---------kV 18
MOCV ----------------kV 15.3
Nominal Current-------kV 10
Residual voltage of steep impulse----at 5kA(kV) 53.3
8/20µS Residual voltage of lightning impulse current kV(Peak value)-----at 5kA(kV) 49.4
Residual voltage of switching impulse current kV (peak value)----at 1kA (kV) 37.8
1mA D.C reference voltage (kV) 25.5
Line discharge level 1
2mS long duration impulse current A 400
4/10µS High current impulse kA 100
Lightning impulse withstand kV 150
Power frequency voltage withstand(dry/wet)kV 38
0.1S TOV--------------kV 21.6
1S TOV----------------kV 20.7
10S TOV---------------kV 19.8
1200S TOV-------------kV 18
Creepage distance ----mm 596
Material employed in series non-linear resistor Zinc Oxide

About us:

 

Yongde holds the quality policy of being 'the technical forerunner, supreme in quality, supremacy of customers, and innovative progressing', so that our products and services successfully satisfied our users. We warmly welcome friends and customers from home and abroad to contact for exchanges and corporations. We also welcome feedbacks from our user communities.18KV Silicon Rubber Metal Oxide Station Class Surge Lightning Arresters for Transformer Protection